5925-00-552-5959 CIRCUIT BREAKER Index 5325-00-552-5966 STUD,TURNLOCK FASTENER

National Stock Number:
5925-00-552-5960

Federal Supply Class:
5925

National Item Identification Number:
005525960

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
DMS 78012B16236DLA LAND AND MARITIME DBA ENGINEERING AND TECHNICAL SUPPORT DIV DOCUMENT STANDARDIZATION DIVISION (VENDOR ITEM DRAWINGS)
TN231100S271669GENERAL ELECTRIC CO SWITCHGEAR AND CONTROL DIVISION OF APPARATUS GROUP


Techincal Specification:
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH4.250 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH0.750 INCHES NOMINAL
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE TWO
BODY LENGTH5.000 INCHES NOMINAL
BODY STYLEMULTIPOLE-SINGLE ACTUATOR TYPE
BODY WIDTH4.750 INCHES NOMINAL
BOSS HEIGHT0.312 INCHES NOMINAL
CASE MATERIALPLASTIC
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH3.625 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH1.688 INCHES NOMINAL
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
FREQUENCY IN HERTZ60.0 ALL LOCATIONS
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS500.0 AC AND 250.0 DC ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE100.0 AMPERES AC AND 100.0 AMPERES DC ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS10000.0 AC AND 5000.0 DC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY6 UNTHREADED HOLE
MOUNTING SURFACE TO TERMINAL END DISTANCE4.625 INCHES NOMINAL
RESET METHODMANUAL
POLE QUANTITY3
SPECIAL FEATURESSHUNT TRIP COIL RATED 32V AND SPST AUXILIARY SWITCH CONNECTED IN SERIES W/SHUNT TRIP COIL
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT10.000 MINIMUM AT 200 PCT AND 110.000 MAXIMUM AT 200 PCT ALL LOCATIONS
TRIP RELEASE AMBIENT TEMP RATING50.0 DEG CELSIUS NOMINAL ALL LOCATIONS
TRIP RELEASE CHARACTERISTICINSTANTANEOUS AND TIME DELAY ALL LOCATIONS
TRIP RELEASE METHODTHERMAL-MAGNETIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT135.0 ALL LOCATIONS
UNTHREADED MOUNTING HOLE DIAMETER0.375 INCHES NOMINAL
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
TERMINAL TYPE AND QUANTITY6 COMPRESSION