5945-00-518-7760 FLASHER,THERMAL Index 5950-00-518-7769 COIL,RADIO FREQUENCY

National Stock Number:
5925-00-518-7763

Federal Supply Class:
5925

National Item Identification Number:
005187763

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
TF12607024446GENERAL ELECTRIC COMPANY


Techincal Specification:
OVERALL WIDTH2.750 INCHES NOMINAL
UNTHREADED MOUNTING HOLE DIAMETER0.281 INCHES NOMINAL
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
ACTUATOR FUNCTIONTRIP W/SEPARATE RESET
ARC QUENCHING METHODDEION
SPECIAL FEATURESMTG HOLES SPACED 7.250 IN. C TO C
POLE QUANTITY2
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE70.0 AMPERES AC AND
70.0 AMPERES DC ALL LOCATIONS
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
TERMINAL TYPE AND QUANTITY4 SCREW
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS600.0 AC AND
250.0 DC ALL LOCATIONS
TRIP RELEASE CHARACTERISTICINSTANTANEOUS AND
TIME DELAY ALL LOCATIONS
RESET METHODMANUAL
MOUNTING FACILITY TYPE AND QUANTITY2 UNTHREADED HOLE
CASE MATERIALPLASTIC
TRIP RELEASE METHODTHERMAL-MAGNETIC ALL LOCATIONS
FREQUENCY IN HERTZ60.0 ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS15000.0 AC AND
15000.0 DC ALL LOCATIONS
TRIP RELEASE DUTY CYCLECONTINUOUS ALL LOCATIONS
TRIP RELEASE AMBIENT TEMP RATING25.0 DEG CELSIUS NOMINAL ALL LOCATIONS
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT400.000 MINIMUM AT 125 PCT AND
6000.000 MAXIMUM AT 125 PCT AND
52.000 MINIMUM AT 200 PCT AND
135.000 MAXIMUM AT 200 PCT AND
21.000 MINIMUM AT 300 PCT AND
42.000 MAXIMUM AT 300 PCT ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT122.0 ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
OVERALL LENGTH9.375 INCHES NOMINAL
OVERALL HEIGHT4.812 INCHES NOMINAL