5945-00-504-5358 RELAY,ELECTROMAGNETIC Index 5945-00-504-5365 RELAY,ROTARY

National Stock Number:
5925-00-504-5364

Federal Supply Class:
5925

National Item Identification Number:
005045364

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
12Z13114-610001NAVAIR AND NAVSEA MANAGED ORIGINAL DESIGN ACTIVITY DWG NOT MATERIAL/PARTS SUPPLIER
12Z13114-694135NAVAL ORDNANCE STANDARDS
CR1061H2A24446GENERAL ELECTRIC COMPANY
CR1061H2A81893GENERAL ELECTRIC CO LYNN RIVER WORKS


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONBETWEEN POLE ONE AND TWO
BODY STYLERECTANGULAR DIMENSIONAL ENVELOPE
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
FREQUENCY IN HERTZ60.0 ALL LOCATIONS
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDDUSTPROOF
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPENONTRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
OVERALL HEIGHT1.750 INCHES NOMINAL
OVERALL LENGTH2.375 INCHES NOMINAL
OVERALL WIDTH1.844 INCHES NOMINAL
MATERIALPLASTIC CASE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE3.5 AMPERES AC ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS10000.0 AC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY4 UNTHREADED HOLE
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS220.0 AC ALL LOCATIONS
POLE QUANTITY2
RESET METHODMANUAL
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
TERMINAL TYPE AND QUANTITY4 SCREW
TRIP RELEASE AMBIENT TEMP RATING40.0 CELSIUS NOMINAL ALL LOCATIONS
TRIP RELEASE CHARACTERISTICINSTANTANEOUS AND TIME DELAY ALL LOCATIONS
TRIP RELEASE METHODTHERMAL ALL LOCATIONS
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT120.000 MAXIMUM AT 200 PCT ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 ALL LOCATIONS
UNTHREADED MOUNTING HOLE DIAMETER0.196 INCHES NOMINAL


Click here to Register for Free 30-day Trial