ACTUATOR FUNCTION | TRIP-RESET |
ACTUATOR POSITION DESIGNATION | AT EACH POLE |
CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE AND TWO LINKED |
FRAGILITY FACTOR | MODERATELY RUGGED |
FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | CORROSION RESISTANT |
INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
MANUAL ACTUATOR TYPE AND QUANTITY | 2 TOGGLE |
MATERIAL | PLASTIC CASE |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 30.0 AMPERES AC ALL LOCATIONS |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 AC ALL LOCATIONS |
MOUNTING FACILITY TYPE AND QUANTITY | 2 THREADED HOLE |
NOMINAL THREAD SIZE | 0.138 INCHES |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC ALL LOCATIONS |
POLE QUANTITY | 2 |
RESET METHOD | MANUAL |
SPECIFICATION/STANDARD DATA | 81348-W-C-375/20-005 GOVERNMENT SPECIFICATION |
STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
TERMINAL TYPE AND QUANTITY | 4 COMPRESSION |
TEST DATA DOCUMENT | 81348-W-C-375/20 SPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTING GENERAL TYPE DATA ON CERTAIN ENVIRONMENTAL AND PERFORMANCE REQUIREMENTS AND TEST CONDITIONS THAT ARE SHOWN AS "TYPICAL", "AVERAGE", "NOMINAL", ETC.). |
THREAD QUANTITY PER INCH | 32 |
THREAD SERIES DESIGNATOR | UNC |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 40.000 MINIMUM AT 200 PCT AND 100.500 MAXIMUM AT 200 PCT ALL LOCATIONS |
TRIP RELEASE AMBIENT TEMP RATING | 25.0 CELSIUS NOMINAL ALL LOCATIONS |
TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 135.0 ALL LOCATIONS |