2810-00-479-3809 BEARING-VALVE ROCKER Index 6105-00-479-3812 ARMATURE,MOTOR

National Stock Number:
5925-00-479-3811

Federal Supply Class:
5925

National Item Identification Number:
004793811

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
150-074952151CONTINENTAL ELECTRONICS CORP
CD3-A2A3A3-AB-2-480-374193EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT EACH POLE
ARC QUENCHING METHODMAGNETIC BLOWOUT
AUXILIARY SWITCH FUNCTION AND QUANTITY1 ALARM
BODY LENGTH4.750 INCHES NOMINAL
BODY STYLEMULTIPOLE-MULTIPLE ACTUATOR TYPE
BODY WIDTH3.093 INCHES MAXIMUM
BOSS HEIGHT0.219 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH2.052 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH3.550 INCHES NOMINAL
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
CUBIC MEASURE63.406 CUBIC INCHES
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH2.750 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH2.052 INCHES NOMINAL
EXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE, TWO, AND THREE LINKED
FRAGILITY FACTORMODERATELY RUGGED
FREQUENCY IN HERTZ50.0 OR 60.0 ALL LOCATIONS
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT AND HUMIDITY RESISTANT
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY3 TOGGLE
MATERIALPLASTIC CASE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE2.0 AMPERES AC ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS5000.0 AC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY6 THREADED BUSHING W/PANEL SEAL
MOUNTING SURFACE TO TERMINAL END DISTANCE4.000 INCHES NOMINAL
NOMINAL THREAD SIZE0.138 INCHES
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS480.0 AC ALL LOCATIONS
POLE QUANTITY3
PRECIOUS MATERIAL AND LOCATIONCONTACT SURFACES SILVER
PRECIOUS MATERIALSILVER
RESET METHODMANUAL
SPECIAL FEATURESVOLTAGE PROTECTION BARRIERS BETWEEN POLES
SPECIAL HANDLING FEATUREMAGNETIC
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
SWITCH CONTACT ARRANGEMENTSINGLE POLE, DOUBLE THROW
SWITCH CURRENT RATING AND TYPE IN AMPS5.0 AC AND 1.0 DC
SWITCH LOCATION AND POSITION DESIGNATIONINTERNAL AT POLE ONE
SWITCH TERMINAL TYPETAB, SOLDER LUG
SWITCH VOLTAGE RATING AND TYPE IN VOLTS1215.0 AC AND 50.0 DC
TERMINAL TYPE AND QUANTITY6 THREADED STUD
THREAD QUANTITY PER INCH32
THREAD SERIES DESIGNATORUNC
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT0.350 MINIMUM AT 200 PCT AND 1.000 MAXIMUM AT 200 PCT ALL LOCATIONS
TRIP RELEASE CHARACTERISTICINSTANTANEOUS AND TIME DELAY ALL LOCATIONS
TRIP RELEASE METHODMAGNETIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 ALL LOCATIONS
UNPACKAGED UNIT WEIGHT2.000 POUNDS NOMINAL