CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
MATERIAL | PLASTIC CASE |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 1600.0 AMPERES AC ALL LOCATIONS |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 75000.0 AC ALL LOCATIONS |
MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 500.0 AC ALL LOCATIONS |
POLE QUANTITY | 3 |
RESET METHOD | MANUAL |
STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
TERMINAL TYPE AND QUANTITY | 6 PIN |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 150.000 MINIMUM AT 300 PCT AND 700.000 MAXIMUM AT 300 PCT ALL LOCATIONS |
TRIP RELEASE AMBIENT TEMP RATING | 50.0 CELSIUS NOMINAL ALL LOCATIONS |
TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS AND TIME DELAY ALL LOCATIONS |
TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 200.0 ALL LOCATIONS |
ULTIMATE TRIP TIME PER POLE IN SECONDS | 160.000 MINIMUM AND 2000.000 MAXIMUM ALL LOCATIONS |
UNTHREADED MOUNTING HOLE DIAMETER | 0.406 INCHES NOMINAL |