5945-00-472-0573 SOLENOID,ELECTRICAL Index 5930-00-472-0581 SWITCH,REED

National Stock Number:
5925-00-472-0575

Federal Supply Class:
5925

National Item Identification Number:
004720575

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
70-341-1074193EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV
990C668H1018323NORTHROP GRUMMAN SYSTEMS CORPORATION
APL1-1176-1081541SENSATA TECHNOLOGIES MARYLAND, INC


Techincal Specification:
ACTUATOR POSITION DESIGNATIONAT POLE ONE
BODY LENGTH2.500 INCHES NOMINAL
BODY STYLESINGLE POLE TYPE
BODY WIDTH0.750 INCHES NOMINAL
BOSS HEIGHT1.125 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH1.938 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH2.062 INCHES NOMINAL
FREQUENCY IN HERTZ60.0 SINGLE LOCATION
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDHUMIDITY RESISTANT AND SHOCK RESISTANT AND VIBRATION RESISTANT
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP SINGLE LOCATION
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS115.0 AC SINGLE LOCATION
MATERIALPLASTIC CASE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE4.0 AMPERES AC SINGLE LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS2000.0 AC SINGLE LOCATION
MOUNTING FACILITY TYPE AND QUANTITY2 THREADED STUD
MOUNTING SURFACE TO TERMINAL END DISTANCE2.611 INCHES NOMINAL
NOMINAL THREAD SIZE0.190 INCHES
POLE QUANTITY1
PRECIOUS MATERIALSILVER
PRECIOUS MATERIAL AND LOCATIONSTUD AND NUT EXTERNAL SURFACES SILVER
RESET METHODAUTOMATIC
TERMINAL TYPE AND QUANTITY2 THREADED STUD
THREAD SERIES DESIGNATORUNF
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT1.500 NOMINAL AT 100 PCT AND 1.000 NOMINAL AT 125 PCT AND 0.120 NOMINAL AT 300 PCT SINGLE LOCATION
TRIP RELEASE AMBIENT TEMP RATING40.0 FAHRENHEIT MINIMUM AND 115.0 FAHRENHEIT MAXIMUM SINGLE LOCATION
TRIP RELEASE CHARACTERISTICTIME DELAY SINGLE LOCATION
TRIP RELEASE METHODMAGNETIC-HYDRAULIC SINGLE LOCATION
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 SINGLE LOCATION


Click here to Register for Free 30-day Trial